ANALISIS DAMPAK PENEMPATAN ALAT PENGUKUR DAN PEMBATAS (APP) TERHADAP BEBAN (Aplikasi: Bandara Internasional Minang Kabau)
Abstract
AbstractDistribution channels and concrete substation PT. PLN is the location Aviation Authority
office. Air network is not allowed in the Airport Authority, the location of the barrier and
Measuring Equipment (APP) placed near the concrete substation. The distance between the
substation building concrete with Class II BIM Port Health Ketaping Pariaman is 700 meters.
Attached power system Phasa P2/33 3 kVA and is the type of cable used NYFGbY ground
cable. In the distribution network located far from the load, rating barrier for 50 Ampere
power used, the size of the cable cross-section used for the 700 meter channel length is 4 x 35
mm2. For the channel length of 10 meters is used a large cross-section cable NYY 4 x 6 mm2.
To drop the voltage channel 700 meters long and 10 meters of copper cable core CU = 7.9
Volts and 2.5 Volts. Loss and Loss for power (losses) for a distance of 700 meters of channel
length with copper cable and 50 Ampere load when the load is 100% 1,890,000 Watt. Loss
and Loss for power (losses) for a distance of 10 meters of channel length with copper cable
and 50 Ampere load is 108,000 Watt.