STUDI PERFORMANSI MESIN PENGKONDISIAN UDARA HIBRIDA MENGGUNAKAN KOLEKTOR SURYA VAKUM

Authors

  • Teguh Satria Tanjung Teknik Mesin Univ. Bung Hatta
  • kaidir Panyalai Panyalai Teknik Mesin Univ. Bung Hatta
  • Mulyanef Mesin Mesin Teknik Mesin Univ. Bung Hatta

Abstract

In  general,  the  air  conditioning is  used  to  condition the  indoor  air  that  are  in  the  air  condition during operation.pada condenser and heat dissipates heat in the condenser can be utilized for other functions so that no heat is wasted. Modifying the air conditioning system with the addition of Water Heaterr aims to harness the heat to be discharged to the environment condenser to heat water. Heating tube mounted on a study done by looking at the influence of the COP (Coefficient of Performance), the cooling rate of the room, as well as the rate of vacuum solar water heating dalam.kolektor added with the goal of accelerating the rate of warming water. From the research conducted, the result is that the COP of the air conditioning with the addition of water heater tank (water heater) decreased from 3.56 becomes 3.53 and a decrease in compression power of 968 Kw be 648 Kw. while the maximum temperature that can be achieved is 66,7ºC. COP of the air conditioning with the addition of water heater tank (water heater) and combined with vacuum solar collectors has increased from

3.68 becomes 3.73.